                                        DMT-FP9000-8
- Conventional central 8 areas with LCD screen
- 2 Siren output
- 2 alarm and fault outputs and 2 configurable relay outputs
- Repeater output
- Up to 30 detectors per zone
- End-of-line resistance auto detection
- DMTECH
- Conventional fire alarm panel of 8 zones
- Certificate EN54-2 and EN54-4
- 2 independent siren outputs
- 2 auxiliary alarm and fault outputs
- 2 configurable relay outputs
- Individual output for repeaters
- Capacity for 2 12V batteries
- 4 access levels ((3 user and 1 manufacturer)
- LCD display with menu for advanced programming
| Primary power supply | Switching source 187-252V AC 50-60 Hz 65W max. | 
| Backup power supply | 2 batteries 12VDC (up to 5 Ah). Ensures minimum 72 hours duration. | 
| Available languages | English, French, Spanish, Turkish, Romanian and Russian. | 
| Number of zones | 8 zones, up to 30 detectors by area. | 
| Siren outputs | 2 siren outputs 24VDC. Independent and monitored open collector outputs | 
| Relay outputs | 4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max. | 
| End of line resistance | Areas fully monitored by end-of-line resistance (4.7K) | 
| Auxiliary Output Voltage | 24VDC. Protected by resettable electronic fuse 1.85A | 
| Protection Index | IP30 | 
| Temperature | -5ºC~+45ºC | 
| Material and colour | ABS, colour: White | 
| Dimensions | 310 x 240 x 80 mm | 
| Weight | 1,3Kg | 
| Recommended cable | Fire cable with a minimum section of 1.0mm (18AWG). | 